Unit Type | HANR(H)S | 20 horses | 25 horses | 30 horses | 40 horses | 50 horses | 60 horses |
model | YM71S | YM89S | YM107S | YM140S | YM180S | YM215S | |
Rated heating one (20℃/15℃) |
Heating capacity(KW) | 71 | 89 | 107 | 140 | 180 | 215 |
power(KW) | 16.9 | 21.19 | 25.47 | 33.3 | 42.85 | 51.2 | |
COP | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | 4.2 | |
Rated heating two (-7℃/-8℃) |
Heating capacity(KW) | 40 | 50.25 | 60.5 | 92 | 120 | 145 |
power(KW) | 15.3 | 20.93 | 23.3 | 30.7 | 40 | 48.33 | |
COP | 2.6 | 2.6 | 2.6 | 3 | 3 | 3 | |
Maximum input power | KW | 19.71 | 24.64 | 29.56 | 41.6 | 55 | 66.5 |
input current | A | 35.24 | 44.04 | 52.75 | 74.5 | 109.6 | 132.1 |
Rated water temperature | ℃ | 55 | 55 | 50 | 50 | 50 | 50 |
Maximum outlet temperature | ℃ | 60 | 60 | 60 | 60 | 60 | 60 |
Power form | V/Hz | 380V/50Hz | 380V/50Hz | 380V/50Hz | 380V/50Hz | 380V/50Hz | 380V/50Hz |
heat exchange maximum working pressure | Mpa | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 | 3.0 |
Maximum working pressure of high/low pressure side | Mpa | 3.0/0.8 | 3.0/0.8 | 3.0/0.8 | 3.0/0.8 | 3.0/0.8 | 3.0/0.8 |
Anti-shock level | / | Class I | Class I | Class I | Class I | Class I | Class I |
degree of protection | / | IPx4 | IPx4 | IPx4 | IPx4 | IPx4 | IPx4 |
Unit noise | less than or equaldB(A) | 78 | 78 | 78 | 86 | 86 | 86 |
Inlet and outlet water pressure difference | Kpa | 40 | 40 | 40 | 40 | 40 | 40 |
The scope of work | ℃ | -10~45 | -10~45 | -10~45 | -10~45 | -10~45 | -10~45 |
Dimensions (L/W/H) | mm | 1750*1060*1830 | 1950*1060*1900 | 2300*1110*2200 | 2400*1200*2400 | 2400*1200*2400 | 2400*1200*2400 |
Host takeover size | National standard | DN50 outer teeth | DN50 outer teeth | DN65 flange | DN65 flange | DN65 flange | DN65 flange |
equipment weight | kg | 650 | 700 | 850 | 1400 | 1600 | 1700 |